如果安裝了控制選項,并且其中一個開關(guān)分配給SETPOINT ACCESS(設(shè)定點訪問),則設(shè)定點訪問開關(guān)和軟件設(shè)定點訪問將作為邏輯and(與)。也就是說,在啟用設(shè)置點訪問之前,必須滿足這兩個條件。假設(shè)設(shè)定點訪問開關(guān)激活設(shè)置為關(guān)閉,則根據(jù)按下存儲鍵時出現(xiàn)的條件,將顯示以下閃爍消息。]]設(shè)置點]]S1 PQM設(shè)置]COM1 RS485]串行端口MODBUS通信地址:1 COM1波特率:9600波特率COM1奇偶性:無]]設(shè)置點]]S2系統(tǒng)設(shè)置設(shè)置點范圍:1至255;步驟1范圍:1200、2400、4800、9600、19200范圍:無、偶數(shù)、奇數(shù)]首選項]]設(shè)置點訪問]]COM2 RS485]串行端口COM2波特率:9600 BAUD COM2奇偶性:無]前面板RS232]串行端口RS232波特率:96000 BAUD RS232奇偶性:NONE MODBUS通信地址:為PQM輸入1到255之間的唯一地址。所選地址用于所有三個串行通信端口。用地址0發(fā)送的消息是一條廣播消息,所有PQM都將偵聽該消息,但不響應(yīng)
If the control option is installed and one of the switches is assigned to SETPOINT ACCESS, the setpoint access switch and the software setpoint access will act as a logic AND. That is, both conditions must be satisfied before setpoint access will be enabled. Assuming the setpoint access switch activation is set to closed, the following flash messages will appear depending upon the condition present when the store key is pressed. ]] SETPOINTS ]] S1 PQM SETUP ] COM1 RS485 ] SERIAL PORT MODBUS COMMUNICATION ADDRESS: 1 COM1 BAUD RATE: 9600 BAUD COM1 PARITY: NONE ]] SETPOINTS ]] S2 SYSTEM SETUP SETPOINT Range: 1 to 255; Step 1 Range: 1200, 2400, 4800, 9600, 19200 Range: NONE, EVEN, ODD ] PREFERENCES ] ] SETPOINT ACCESS ] ] COM2 RS485 ] SERIAL PORT COM2 BAUD RATE: 9600 BAUD COM2 PARITY: NONE ] FRONT PANEL RS232 ] SERIAL PORT RS232 BAUD RATE: 9600 BAUD RS232 PARITY: NONE MODBUS COMMUNICATION ADDRESS: Enter a unique address from 1 to 255 for the PQM. The selected address is used for all three serial communication ports. A message sent with address 0 is a broadcast message to which all PQMs will listen but not respond