GE 8102-HO-IP通道模擬輸出模塊
1.產(chǎn) 品 資 料 介 紹:
中文資料:
節(jié)點(diǎn)ID交換機(jī)在主機(jī)機(jī)箱中安裝GE 8102-HO-IP之前,必須通過(guò)配置交換機(jī)S6來(lái)設(shè)置所需的節(jié)點(diǎn)ID。網(wǎng)絡(luò)中的每個(gè)節(jié)點(diǎn)都必須有一個(gè)唯一的節(jié)點(diǎn)ID。有關(guān)交換機(jī)S6的位置,請(qǐng)參見(jiàn)第35頁(yè)圖2-1。開(kāi)關(guān)S6是一個(gè)八位開(kāi)關(guān),對(duì)應(yīng)于8條節(jié)點(diǎn)ID選擇信號(hào)線。8個(gè)節(jié)點(diǎn)ID選擇行允許從0到$FF(小數(shù)點(diǎn)后255)的任何節(jié)點(diǎn)ID。開(kāi)關(guān)S6,位置1對(duì)應(yīng)于最低有效節(jié)點(diǎn)ID線,位置8對(duì)應(yīng)于最高有效節(jié)點(diǎn)ID線上。將開(kāi)關(guān)位置設(shè)置為ON會(huì)將節(jié)點(diǎn)ID線設(shè)置為低(0),而將位置設(shè)置為OFF會(huì)將節(jié)點(diǎn)標(biāo)識(shí)線設(shè)置為高(1)。
跳線E5用于為GE 8102-HO-IP配置冗余或非冗余傳輸模式以及roque master的選擇。在引腳1和2上安裝跳線分流器可選擇非冗余(快速)傳輸模式。移除(省略)跳線分流器可將板配置為冗余網(wǎng)絡(luò)傳輸模式。在引腳3和4上安裝跳線分流器將禁用流氓主機(jī)0功能。從引腳3和4上卸下跳線可啟用rogue master 0功能。在引腳5和6上安裝跳線分流器將禁用流氓主機(jī)1功能。拆除引腳5和6上的跳線分流器可啟用流氓主機(jī)1功能。請(qǐng)參閱下表2-2配置跳線E5
英文資料:
Node ID Switch Prior to installing the GE 8102-HO-IP in the host chassis, the desired node ID must be set by configuring Switch S6. Each node in network must have a unique node ID. See Figure 2-1 on page 35 for the location of Switch S6. Switch S6 is an eight position switch, which corresponds to 8 node ID select signal lines. The 8 node ID select lines permit any node ID from 0 to $FF (255 decimal). Switch S6, position 1 corresponds to the least significant node ID line and position 8 corresponds to the most significant node ID line. Setting the switch position to ON sets the node ID line low (0), while setting the position to OFF sets the node ID line high (1).
Jumper E5 is used to configure the GE 8102-HO-IP for redundant or non-redundant transfer modes as well as the selection of roque master. Installing a jumper shunt on pins 1 and 2 selects the non-redundant (fast) transfer mode. Removing (Omitting) the jumper shunts configures the board for the redundant network transfer mode. Installing a jumper shunt on pins 3 and 4 disables rogue master 0 function. Removing the jumper from pins 3 and 4 enables rogue master 0 function. Installing a jumper shunt on pins 5 and 6 disables the rogue master 1 function. Removal of the jumper shunt on pins 5 and 6 enables the rogue master 1 function. See Table 2-2 below to configure Jumper E5
2.產(chǎn) 品 展 示

3.主 營(yíng) 品 牌

本篇文章出自瑞昌明盛自動(dòng)化設(shè)備有限公司官網(wǎng),轉(zhuǎn)載請(qǐng)附上此鏈接:http://m.wzljsf.com